dc.contributor.authorKelsey, Jimen_US
dc.date.accessioned2007-05-14T14:41:18Z
dc.date.available2007-05-14T14:41:18Z
dc.date.issued1996en_US
dc.identifier.citationKelsey, J. (1996). The Energy Use Implications of Design Choices in Commercial Buildings. Master's Thesis, University of Wisconsin-Madison.en_US
dc.identifier.urihttp://digital.library.wisc.edu/1793/7767
dc.descriptionUnder the supervision of Professors John Mitchell and William Beckman; 124pp.en_US
dc.description.abstractThe process of designing a heating and cooling system for a commercial building usually proceeds from building design to design of an HVAC system that can meet the loads in the building. The purpose of this thesis is to focus instead on what can be done to minimize buildings loads, by making the best design choices. Wisconsin and other states are currently in the process of adopting their building energy codes to conform to ASHRAE/EIS standard 90.1-1989. The Energy Policy Act of 1992 requires that each state develop a commercial building code that is at least as stringent as this standard. This thesis investigates the effect of these revised codes on the energy use of new buildings. A case study of two common building types is used to quantify the effect of the codes on building loads. The thesis is a case study of two commercial buildings; using an office building and a retail building. These types of buildings were chosen because, together, they make up a large portion of the energy consumption and peak demand in the commercial building stock. For each of the buildings, TRNSYS computer simulations were used to estimate the energy use in the building. TRNSYS decks were created from data gathered from building plans and site visits. The computer simulations were validated using monthly energy bills from the two buildings. Computer simulations were used to estimate the effect of compliance to the ASHRAE standard on the energy use of the buildings. The building models were modified to include the addition of insulation to roofs, walls and building perimeters that would be required by the code. A life-cycle savings method was used in conjunction with the building models to determine what level of insulation would be the most cost effective design for the buildings. These optimal levels were compared to the ASHRAE required amount of insulation for five cities in the U.S. The energy and cost savings resulting from meeting the prescriptive version of the ASHRAE Standard 90.1 were found to be significant. In both of the buildings studied, building owners would have saved money had the buildings been built to comply with the standard. The simple payback period for individual measures required by the code varied over a wide range. Some measures would have paid for themselves instantly, in cooling equipment cost savings. Other measures had payback periods up to 24 years. Taking all the required measures together yielded payback periods of 6 to 8 years. Two daylighting strategies were also evaluated using the retail building model. The TRNSYS deck and building input description were modified to simulate the addition of skylights and sawtooth roof monitors to the building. The building models included both the direct effects of lighting energy savings, and the indirect effects on heating and cooling loads in the building. A life-cycle cost analysis was conducted to determine the optimal area of skylights or monitors to add, and the energy and cost savings associated with each. The daylighting measures offered payback periods equal to or less than the insulation measures required by ASHRAE Standard 90.1. Daylighting measures yielded cooling energy savings, and decreased electricity bills, while ASHRAE code compliance mainly provided energy savings from heating loads met with natural gas. Should energy planners want to focus more on electricity savings rather than natural gas, one way to do it would be to facilitate the installation of more daylighting in commercial buildings.en_US
dc.description.sponsorshipSponsored by ASHRAE, The Energy Center of Wisconsin, and The American Public Power Association.en_US
dc.format.extent17290 bytes
dc.format.extent124327 bytes
dc.format.extent259037 bytes
dc.format.extent51584 bytes
dc.format.extent22743 bytes
dc.format.extent480851 bytes
dc.format.extent54602 bytes
dc.format.extent11699 bytes
dc.format.extent8729 bytes
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/pdfen_US
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/octet-stream
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/pdf
dc.format.mimetypeapplication/pdf
dc.publisherUniversity of Wisconsin-Madisonen_US
dc.subjectThesis (M.S.)--University of Wisconsin--Madison, 1996.en_US
dc.subjectDissertations Academic Mechanical Engineering.en_US
dc.subjectUniversity of Wisconsin--Madison. College of Engineering.en_US
dc.titleThe Energy Use Implications of Design Choices in Commercial Buildingsen_US